Summation of Alternating Currents

Info Letter No. 4

General Info

For the parallel connection of power sources, the principle of superposition applies, when all resources have a linear behaviour. This behaviour is the case with current transformers within the allowable load range and below a few thousand Hertz. It should be noted that in principle and device technically only simultaneous instantaneous values are added, not effective values!

Through the common load resistor RL of parallel current transformers a current flows that corresponds to the arithmetic sum of the instantaneous values of all the currents. It is assumed that the current transformers provide superimposed currents and the frequency limits (highest order of the harmonics) are not exceeded.

The arithmetic sum of the instantaneous values is not only dependent on the amount, but also the sign of the individual currents, so that for the summation the polarity of the current sources must be considered. With alternating currents of the same direction of energy flow, the polarity is related to the secondary terminals S1 (k) and S2 (l) of the current transformer.

Waveform of the Total Current

When summing equal frequency sinusoidal currents, the curve of iS has the form of a sinusoidal curve, with currents of unequal frequency the waveform of the total current i is no longer sinusoidal.

Waveform of the total current for the summation of three currents
a) with the same frequency
b) with different frequencies

Sum of the Instantaneous Values

For the three-phase three-wire network with the same frequency sinusoidal currents, the simultaneous instantaneous values are ideally zero.

Effective Value of the Total Current

For the calculation of the effective value of the total current from the momentary values of current with an arbitrary frequency/waveform the following applies:

I_{\sum} = \sqrt{\frac{1}{T}\int_{T}^{0}(i_{0} +i_{1}+i_{2}+...+i_{n})^{2} dt }
i_{0} +i_{1}+i_{2}+...+i_{n}

Arithmetic sum of the simultaneous current components

For the calculation only of the effective values of currents with different frequencies (e.g. equal value/ fundamental with harmonics) the following also applies:

I_{\sum} = \sqrt{I^{2}_{0} +I^{2}_{1}...+I^{2}_{n} }

I0 = Effective value of the direct current
I1 = Effective value of the fundamental
In = Effective value of the highest harmonic

Automatic Voltage Regulation With REGSys® – Proven a Thousand Times Over, Multifunctional and Flexible

LVRSys® – the Cost and Time Efficient Alternative to Line/Grid Expansion

Cost and Time Efficient, Easy to Install, Flexible & Low/No-Maintenance

Need More Information?

Contact Us!


Contact

Info-Letters

Click Through Our Info Letter Series

News From the Product Groups

LVRSys® | Power Quality | EORSys | REGSys® | – News

General Knowledge

Voltage Measurement Can Improve the Quality of Supply

A short study by EWI and Fraunhofer IEG shows that mandatory voltage measurements and stricter regulation of voltage quality are necessary to ensure grid stability in Germany in light of the energy transition.

Read more

Special Publication

LVRSys®: It’s All About the Right Voltage

Summary Stable voltage quality is becoming increasingly important in modern distribution grids. Due to the growing feed-in of renewable energies […]

Read more

General Knowledge

Power in Multiphase Systems

This technical report highlights the special features of power transmission in three-phase systems and offers valuable insights into the optimisation and analysis of modern power grids.

Read more

Webinar

»PQMobil« Webinar: New Features/Functions for Your PQ-Box/es: Presentation of WinPQ mobil V8 & V7 legacy

Webinar recording from 2025-07-29: »PQMobil - New Features/Functions for Your PQ-Box/es: Presentation of WinPQ mobil V8 & V7 legacy«.

Read more

Webinar

»EORSys« EOR-1DS – the Economical Fault Indicator for the Secondary Substation

Webinar recording from 2025-07-16: »EORSys - EOR-1DS - the Economical Fault Indicator for the Secondary Substation«.

Read more

Blogpost

Visit From the Rudolf Diesel Technical School at A. Eberle

We were happy to welcome you, Rudolf-Diesel-Fachschule! Yesterday, we had the pleasure of welcoming two classes of future electrical engineering technicians from the Rudolf-Diesel-Fachschule Nürnberg to our company in Nuremberg.

Read more

Blogpost

TOP 100 Awards 2025: Innovation for the Energy Future

💡 As part of the TOP 100 Awards 2025, we were honored to receive a special recognition last week in Mainz – personally presented by TV host and science journalist Ranga Yogeshwar.

Read more

Blogpost

University Excursion: Pentecost Excursion of the Friedrich-Alexander-University Erlangen-Nuremberg (FAU)

As a company dedicated to innovation, education, and the energy transition, we are pleased to have once again supported the Whitsun excursion of Friedrich-Alexander University Erlangen-Nuremberg (FAU) this year.

Read more

Blogpost

Further Growth at A. Eberle

Welcome to the team! We welcome our new colleagues at A. Eberle.

Read more

General Knowledge

Voltage Stabilisation

In this article, you will learn why voltage stabilisation in high, medium and low-voltage grids plays a central role in safe and efficient grid operation. You will learn the basics of ‘voltage stabilisation’ and get to know modern control solutions to reliably compensate for voltage fluctuations and ensure sustainable grid quality.

Read more

Blogpost

Specialist Training on Power Quality

On 27 May 2025, everything revolved around electricity, faults and how to recognise them in a specialist training course on power quality at the Balthasar Neumann Technical Centre in Trier (BNT).

Read more

Webinar

»PQSys« Webinar: PQ-Monitoring & Feeder Current Measurement in Low-Voltage Grids 3

Webinar recording from 2025-05-14: »PQSys - PQ-Monitoring & Feeder Current Measurement in Low-Voltage Grids - part 3«.

Read more

Webinar

»PQMobil« Webinar: Power Quality Analysis in Public & Industrial Power Grids – Part 3

Webinar recording from 2025-04-02: »PQMobil - Power Quality Analysis in Public & Industrial Power Grids – Part 3«.

Read more

Webinar

»LVRSys®« Webinar: The Solution for Voltage Stability Problems

Webinar recording from 2025-03-19: »LVRSys® - The Solution for Voltage Stability Problems«.

Read more

Training Video

»PQMobil« Training Video 7: Measurement Data

This video is all about the measurement data. What data does the PQ-Box record and what is the best way to configure it beforehand?

Read more

Special Publication

Renewable Energy Solutions (RES) – Pilot Project in South Africa for Efficient Voltage Stabilisation With »LVRSys®«

This application report shows the successful use of the »LVRSys®« low voltage regulation system in the Siemens data centre in Midrand, South Africa. Read here how »LVRSys®« reliably stabilises the voltage in critical infrastructure.

Read more

Blogpost

First »LVRSys® – Low-Voltage Regulation« System in South Africa

We are excited to share another milestone in grid stability and energy efficiency: the first »LVRSys®« - low-voltage regulation system in south africa has been successfully commissioned!

Read more

Webinar

»PQSys« Webinar: Presentation: »PQI-LV« – The New PQ-Analyser for Transparency in the Low-Voltage Grid

Webinar recording from 2025-02-19: »PQSys - Presentation: »PQI-LV« - The New PQ-Analyser for Transparency in the Low-Voltage Grid«.

Read more

Training Video

»REGSys®« Training Video 8: Overview SCL-Config for IEC 61850

In this video you will learn how you can export a CID file, how to adjust the IED name and working with the SCL-Config.

Read more

Training Video

»REGSys®« Training Video 7: How to Use the Winconfig Software

In this video you will learn how to create a new parameter file, how to upload setting files or download setting files from the Scada card and what kind of parameters a setting file contains.

Read more

Training Video

»REGSys®« Training Video 6: Firmware Update via Winconfig

In this video you will learn when it is reasonable to use the WinConfig for a firmware update and how to do a firmware update with the WinConfig.

Read more

Training Video

»REGSys®« Training Video 5: Firmware Update via RPL2

In this video you will learn how to create a physical connection before the firmware update, how to use the RPL2 software and how to do a small test after the firmware update.

Read more

Training Video

»REGSys®« Training Video 4: Changing the Default Password

In this video you will learn how to connect the SCADA card to your computer, start the software WinConfig and change the default password and define a new one.

Read more

Training Video

»REGSys®« Training Video 3: Changing IP Address via Winconfig

In this video you will learn how to define a new IP address, how to interpret the “States of detected boards” and how to determine the port numbers of the physical ports.

Read more

Training Video

»REGSys®« Training Video 2: Changing IP-Address via Webserver

In this video you will learn how to access the web server, how to change the network settings in the web server.

Read more

Contact request:



* Mandatory

Your data is being processed

a-eberle kontakt newsletter ×

Unser Newsletter zum Thema »LVRSys®« – Niederspannungsregelung

Möchten Sie weitere interessante Inhalte wie Fachberichte, Anwendungsbeispiele und Schulungsvideos zum Thema »LVRSys®« – Niederspannungsregelung erhalten?

Melden Sie sich hier kostenfrei an:

Vielen Dank für Ihre Anmeldung zu unserem Newsletter zum Thema »LVRSys®« – Niederspannungsregelung

Hier glangen Sie zum Download: